Pts-6 V2.0 May 2026
5/8" or 1/2" compression fittings (also supports PEX/ProPEX) 12" W x 4" D x 12" H Pressure Rating Minimum 20 PSIG required for standard operation Key Features
: It is factory-preset to activate for 6 seconds once every 24 hours . PTS-6 V2.0
: Must be mounted above the finished floor level. Prime-Time Electronic Trap Priming Assembly Surface Mount 5/8" or 1/2" compression fittings (also supports PEX/ProPEX)
: Includes an atmospheric vacuum breaker to prevent backflow into the potable water supply. PTS-6 V2.0
: Uses a specialized manifold to ensure equal water distribution across all connected outlets.
: Supplies a minimum of 2 oz of potable water at 20 PSIG to each connected drain.